Redline Series G60
Miniature Circuit Breakers – Characteristics B, C, D

Technical Specifications
- Thermal Setting In (A): 2 – 63
- Rated Voltage AC Un (V): 240/415
- Minimum Operating Voltage UB min (V): 12
- Tripping Characteristics: B, C, D
- Selectivity Class: 3
- Mechanical/Electrical Endurance: 20,000 / 10,000 operations
- Tropicalisation: 95% RH at 55°C (EN/IEC 60068-2)
- Terminal Capacity (flexible/rigid cable): 25-35 mm²
- Poles: 1, 1+N, 2, 3, 4
- Weight: 120 g per pole
Short-Circuit Capacity (AC acc. to EN/IEC 60898-1)
Poles | Voltage (V) | Icn / Ics (kA) |
---|---|---|
1-4 | 230/400 | 6 |
Short-Circuit Capacity (AC acc. to EN/IEC 60947-2)
Poles | Voltage (V) | Icu (kA) |
---|---|---|
1 | 240 | 10 |
1+N, 2 | 127 | 30 |
1+N, 2 | 240 | 20 |
2 | 415 | 10 |
3, 4 | 240 | 20 |
3, 4 | 415 | 10 |
Product Range
Available current ratings (In) and catalog/reference numbers for characteristics B, C, and D.
Characteristic B
In (A) | Cat. No. | Ref. No. | Packaging (pcs) |
---|---|---|---|
2 | G61B06 | 674692 | 12 |
4 | G61B10 | 674694 | 12 |
6 | G61B16 | 674696 | 12 |
10 | G61B20 | 674697 | 12 |
16 | G61B25 | 674698 | 12 |
20 | G61B32 | 674699 | 12 |
25 | G61B40 | 674700 | 12 |
32 | G61B50 | 674701 | 12 |
40 | G61B63 | 674702 | 12 |
Characteristic C
In (A) | Cat. No. | Ref. No. | Packaging (pcs) |
---|---|---|---|
2 | G61C02 | 674598 | 12 |
4 | G61C04 | 674600 | 12 |
6 | G61C06 | 674601 | 12 |
10 | G61C10 | 674603 | 12 |
16 | G61C16 | 674605 | 12 |
20 | G61C20 | 674606 | 12 |
25 | G61C25 | 674607 | 12 |
32 | G61C32 | 674608 | 12 |
40 | G61C40 | 674609 | 12 |
50 | G61C50 | 674610 | 12 |
63 | G61C63 | 674611 | 12 |
Characteristic D
In (A) | Cat. No. | Ref. No. | Packaging (pcs) |
---|---|---|---|
2 | G61D02 | 674760 | 12 |
4 | G61D04 | 674762 | 12 |
6 | G61D06 | 674763 | 12 |
10 | G61D10 | 674765 | 12 |
16 | G61D16 | 674767 | 12 |
20 | G61D20 | 674768 | 12 |
25 | G61D25 | 674769 | 12 |
32 | G61D32 | 674770 | 12 |
40 | G61D40 | 674771 | 12 |
50 | G61D50 | 674772 | 12 |
63 | G61D63 | 674773 | 12 |
Additional Information
- Approvals / Marking: EN/IEC 60898-1, EN/IEC 60947-2
- Add-on Devices: Auxiliaries, motor operators, add-on RCDs, shunt trips, undervoltage releases, panel board switches, busbars.
- Special Executions: G60S for shipping applications (see separate document).
- Other Versions: Compact MCBs 6 kA (see pages A.61, A.63, A.66), Screwless MCBs 6 kA (see page A.76).
Other Module or Residencials
————–