Technical Specifications

  • Circuit Protection Types: A, B, C, D, E, F, G, X
  • Standards / Marking: EN/IEC 60898-2, DIN VDE 0641, EN/IEC 60947-2
  • Thermal Setting In (A): 0.5 – 63
  • Rated Voltage AC Un (V): 230/400, 250/500/880
  • Minimum Operating Voltage UBmin (V): 12
  • Tripping Characteristics: B, C
  • Mechanical/Electrical Endurance: 20,000 / 10,000 operations
  • Tropicalisation: 95% RH at 55°C (EN/IEC 60068-2)
  • Terminal Capacity (flexible/rigid cable): 25-35 mm²
  • Poles: 1, 2, 4 (Polarity labeling must be respected due to permanent magnet)
  • Weight: 120 g per pole

Short-Circuit Capacity (AC/DC)

Poles Voltage (V) Icn = Ics (kA)
1 125 DC 10
1 250 DC 6
1 230/400 AC 6
2 250 DC 10
2 500 DC 6
2 400 AC 6
4 800 DC 6

Short-Circuit Capacity (EN/IEC 60947-2)

Poles Voltage (V) Icu (kA)
1 220 DC 10 (T=4ms)
2 440 DC 10 (T=4ms)
1 230 AC 6 (4.5kA for 50A and 63A)
2 400 AC 6 (4.5kA for 50A and 63A)
Notes:
  • For 4P execution, open circuit voltage Uco = 1000 V
  • After switching a net with more than 6kA in AC, it should not be used in DC

Product Range - Characteristics B and C

Lorem ipsum dolor sit amet, consectetur adipiscing elit. Ut elit tellus, luctus nec ullamcorper mattis, pulvinar dapibus leo.

Characteristic B

In (A) Cat. No. Ref. No. Packaging (pcs)
0.5 EP101UCB06 673333 12
1 EP101UCB10 673334 12
2 EP101UCB16 673335 12
4 EP101UCB20 673336 12
6 EP101UCB25 673337 12
10 EP101UCB32 673338 12
16 EP101UCB40 673339 12
20 EP101UCB50 673340 12
25 EP101UCB63 673341 12

Characteristic C

In (A) Cat. No. Ref. No. Packaging (pcs)
0.5 EP101UCC0.5 673301 12
1 EP101UCC01 673302 12
2 EP101UCC02 673303 12
4 EP101UCC04 673305 12
6 EP101UCC06 673306 12
10 EP101UCC10 673308 12
16 EP101UCC16 673310 12
20 EP101UCC20 673311 6
25 EP101UCC25 673312 6
32 EP101UCC32 673313 6
40 EP101UCC40 673314 6
50 EP101UCC50 673315 6
63 EP101UCC63 673316 6

Additional Information

  1. Poles and Modules: 1P (1 module), 2P (2 modules), 4P (4 modules). For 4P execution, open circuit voltage Uco = 1000 V.
  2. Applications: Suitable for photovoltaic installations, inverter protection, and general domestic and industrial circuit protection.
  3. Accessories: Add-on RCDs, auxiliary contacts, motor operators, shunt trips, undervoltage releases, panel board switches, and busbars are available. See product catalog for details.

 

Note: Polarity labeling must be respected due to the permanent magnet in the MCB.